chemical pollution resistance class 3C3 IEC 60721-3-3 || dust pollution resistance class 3S3 IEC 60721-3-3
Shock Resistance:
15 gn 11 ms IEC 60068-2-27
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
Ambient Air Temperature For Storage:
-40-70 °C
Product Or Component Type:
variable speed drive
Network Frequency:
50-60 Hz
Type Of Polarization:
no impedance
Line Current:
13.8 A 380 V normal duty) || 10.5 A 380 V heavy duty) || 11.9 A 480 V normal duty) || 9.2 A 480 V heavy duty)
Discrete Input Number:
10
Sampling Duration:
2 ms +/- 0.5 ms DI1...DI8) - discrete input || 5 ms +/- 1 ms DI7, DI8) - pulse input || 1 ms +/- 1 ms AI1, AI2, AI3) - analog input || 5 ms +/- 1 ms AQ1, AQ2) - analog output
Analogue Output Type:
software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits || software-configurable current AQ1, AQ2 0...20 mA 500 Ohm 10 bits
external supply for digital inputs 24 V DC 19-30 V), <1.25 mA overload and short-circuit protection || internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection || internal supply for d
logic output DQ+ 0-1 kHz <= 30 V DC 100 mA || programmable as pulse output DQ+ 0-30 kHz <= 30 V DC 20 mA || logic output DQ- 0-1 kHz <= 30 V DC 100 mA
Discrete Input Type:
DI1...DI8 programmable, 24 V DC <= 30 V)3.5 kOhm || DI7, DI8 programmable as pulse input 0-30 kHz, 24 V DC <= 30 V) || STOA, STOB safe torque off, 24 V DC <= 30 V)> 2.2 kOhm
Apparent Power:
9.9 kVA 480 V normal duty) || 7.6 kVA 480 V heavy duty)
Pollution Degree:
2
Product Certifications:
CSA || UL || TÃV
Accuracy:
+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input || +/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog output
With Safety Function Safely Limited Position (Slp):
FALSE
With Safety Function Safe Direction (Sdi):
FALSE
Maximum Acceleration Under Shock Impact (During Operation):
150 m/s² at 11 ms
China Rohs Regulation:
X
Analogue Input Type:
AI1, AI2, AI3 software-configurable voltage 0...10 V DC 30 kOhm 12 bits || AI1, AI2, AI3 software-configurable current 0...20 mA/4...20 mA 250 Ohm 12 bits
Width:
155 mm
With Safety Function Safely Limited Speed (Sls):
TRUE
Operating Altitude:
<= 3280.84 ft (1000 m) without derating || 1000...4800 m with current derating 1 % per 100 m
Option Card:
slot A communication module Profibus DP V1 || slot A communication module PROFINET || slot A communication module DeviceNet || slot A communication module EtherCAT || slot A communication module CANopen daisy chain RJ45 || slot A communication module
Maximum Deflection Under Vibratory Load (During Operation):
1.5 mm at 2...13 Hz
Rohs Exemption Information:
Yes
Type Of Polarization:
no impedance Modbus serial
Number Of Addresses:
1-247 Modbus serial
Data Format:
8 bits, configurable odd, even or no parity Modbus serial
Prospective Line Isc:
50 kA
Switching Frequency:
2...16 kHz adjustable || 4...16 kHz with derating factor
Maximum Output Voltage:
480.0 V
Depth:
225 mm
Exchange Mode:
half duplex, full duplex, autonegotiation Ethernet IP/Modbus TCP
Maximum Transient Current:
19.8 A 60 s normal duty) || 19.1 A 60 s heavy duty)
Number Of Addresses:
1-247
Linearity Error:
AI1, AI2, AI3 +/- 0.15 % of maximum value analog input || AQ1, AQ2 +/- 0.2 % analog output
4 Quadrant Operation Possible:
TRUE
Physical Interface:
Ethernet || 2-wire RS 485
Noise Level:
56 dB 86/188/EEC
Base Load Current At High Overload:
12.7 A
Marking:
CE
Maximum Switching Current:
relay output R1 resistive, cos phi = 1 3 A 250 V AC || relay output R1 resistive, cos phi = 1 3 A 30 V DC || relay output R1 inductive, cos phi = 0.4 7 ms 2 A 250 V AC || relay output R1 inductive, cos phi = 0.4 7 ms 2 A 30 V DC || relay output R2, R
California Proposition 65:
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Braking To Standstill:
by DC injection
Protection Type:
thermal protection motor || safe torque off motor || motor phase break motor || thermal protection drive || safe torque off drive || overheating drive || overcurrent between output phases and earth drive || overload of output voltage drive || short-c
Insulation Resistance:
> 1 MOhm 500 V DC for 1 minute to earth
Acceleration And Deceleration Ramps:
linear adjustable separately from 0.01...9999 s
Relative Symmetric Network Frequency Tolerance:
0.05
Electromagnetic Compatibility:
electrostatic discharge immunity test level 3 IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 || electrical fast transient/burst immunity test level 4 IEC 61000-4-4 || 1.2/50 µs - 8/20 µs surge im
Relative Humidity:
5-95 % without condensation IEC 60068-2-3
Power Dissipation In W:
forced convection 172 W 380 V 4 kHz || natural convection 44 W 380 V 4 kHz
With Sft Fct Safe Stop 2 (Ss2):
FALSE
Nominal Switching Frequency:
4 kHz
Local Signalling:
local diagnostic 3 LED mono/dual colour) || embedded communication status 5 LED dual colour) || communication module status 2 LED dual colour) || presence of voltage 1 LED red)
Emc Filter:
integrated || with EMC plate option
Isolation:
between power and control terminals
Base Load Current At Low Overload:
16.5 A
Ambient Air Transport Temperature:
-40-70 °C
Asynchronous Motor Control Profile:
variable torque standard || constant torque standard || optimized torque mode
Method Of Access:
slave Modbus TCP
Sustainable Offer Status:
Green Premium product
Degree Of Protection:
UL type 12
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Continuous Output Current:
16.5 A 4 kHz normal duty || 12.7 A 4 kHz heavy duty