thermal protection motor || safe torque off motor || motor phase break motor || thermal protection drive || safe torque off drive || overheating drive || overcurrent between output phases and earth drive || overload of output voltage drive || short-c
Motor Slip Compensation:
can be suppressed || automatic whatever the load || not available in permanent magnet motor law || adjustable
Method Of Access:
slave Modbus TCP
Analogue Input Number:
3
Noise Level:
56 dB 86/188/EEC
Environmental Disclosure:
ENVPEP1706016EN
Environmental Characteristic:
chemical pollution resistance class 3C3 IEC 60721-3-3 || dust pollution resistance class 3S3 IEC 60721-3-3
Regulation Loop:
adjustable PID regulator
Acceleration And Deceleration Ramps:
S, U or customized || linear adjustable separately from 0.01...9999 s
Depth:
297 mm
Product Specific Application:
process for industrial
Minimum Switching Current:
relay output R1, R2, R3 5 mA 24 V DC
Maximum Deflection Under Vibratory Load (During Operation):
half duplex, full duplex, autonegotiation Ethernet IP/Modbus TCP
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
Line Current:
82.7 A 500 V normal duty) || 71.0 A 500 V heavy duty) || 87.7 A 690 V normal duty) || 68.5 A 690 V heavy duty)
Overvoltage Category:
III
Type Of Polarization:
no impedance
Mercury Free:
Yes
Operating Position:
vertical +/- 10 degree
Volume Of Cooling Air:
406 m3/h
Maximum Acceleration Under Vibrational Stress (During Operation):
10 m/s² at 13...200 Hz
Ambient Air Temperature For Storage:
-40-70 °C
Circularity Profile:
ENVEOLI1706016EN
With Sft Fct Safe Stop 2 (Ss2):
FALSE
Analogue Input Type:
AI1, AI2, AI3 software-configurable voltage 0...10 V DC 30 kOhm 12 bits || AI1, AI2, AI3 software-configurable current 0...20 mA/4...20 mA 250 Ohm 12 bits
Communication Port Protocol:
Modbus serial || Modbus TCP || EtherNet/IP
Power Dissipation In W:
forced convection 1075 W 500 V 2.5 kHz || natural convection 268 W 500 V 2.5 kHz
With Safety Function Safe Brake Management (Sbc/Sbt):
TRUE
Device Application:
Industrial Application
Product Destination:
asynchronous motors || synchronous motors
Variant:
with braking chopper || standard version
Rohs Exemption Information:
Yes
4 Quadrant Operation Possible:
TRUE
Product Certifications:
CSA || TÃV || UL
With Safety Function Safe Operating Stop (Sos):
FALSE
With Safety Function Safe Torque Off (Sto):
TRUE
Physical Interface:
Ethernet || 2-wire RS 485
Discrete Output Number:
2
Isolation:
between power and control terminals
With Safety Function Safely Limited Position (Slp):
FALSE
Maximum Transient Current:
99.6 A 60 s normal duty) || 99 A 60 s heavy duty)
Range Of Product:
Altivar Process ATV900
Motor Power Kw:
55.0 kW normal duty || 45.0 kW heavy duty
California Proposition 65:
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Sampling Duration:
2 ms +/- 0.5 ms DI1...DI8) - discrete input || 5 ms +/- 1 ms DI7, DI8) - pulse input || 1 ms +/- 1 ms AI1, AI2, AI3) - analog input || 5 ms +/- 1 ms AQ1, AQ2) - analog output
slot A communication module Profibus DP V1 || slot A communication module PROFINET || slot A communication module DeviceNet || slot A communication module EtherCAT || slot A communication module CANopen daisy chain RJ45 || slot A communication module
Electromagnetic Compatibility:
electrostatic discharge immunity test level 3 IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 || electrical fast transient/burst immunity test level 4 IEC 61000-4-4 || 1.2/50 µs - 8/20 µs surge im
Type Of Polarization:
no impedance Modbus serial
Linearity Error:
AI1, AI2, AI3 +/- 0.15 % of maximum value analog input || AQ1, AQ2 +/- 0.2 % analog output
Product Or Component Type:
variable speed drive
Analogue Output Number:
2
Insulation Resistance:
> 1 MOhm 500 V DC for 1 minute to earth
Prospective Line Isc:
70 kA
Discrete Input Logic:
16 preset speeds
Shock Resistance:
15 gn 11 ms IEC 60068-2-27
Braking To Standstill:
by DC injection
Local Signalling:
local diagnostic 3 LED mono/dual colour) || presence of voltage 1 LED red) || embedded communication status 3 LED dual colour) || communication module status 4 LED dual colour)
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Number Of Addresses:
1-247
Permitted Relative Humidity (During Operation):
class 3K5 according to EN 60721-3
Analogue Output Type:
software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits || software-configurable current AQ1, AQ2 0...20 mA 500 Ohm 10 bits
Base Load Current At Low Overload:
83.0 A
With Safety Function Safe Speed Monitor (Ssm):
FALSE
Supply:
external supply for digital inputs 24 V DC 19-30 V), <1.25 mA overload and short-circuit protection || internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection || internal supply for d
Relay Output Number:
3
Pollution Degree:
2
Height:
630 mm
Maximum Switching Current:
relay output R1 resistive, cos phi = 1 3 A 250 V AC || relay output R1 resistive, cos phi = 1 3 A 30 V DC || relay output R1 inductive, cos phi = 0.4 7 ms 2 A 250 V AC || relay output R1 inductive, cos phi = 0.4 7 ms 2 A 30 V DC || relay output R2, R
Upgradeability:
Upgraded components available
Switching Frequency:
1...4.9 kHz adjustable || 2.5...4.9 kHz with derating factor
Sustainable Offer Status:
Green Premium product
Degree Of Protection:
UL type 1
Ip Degree Of Protection:
IP21
Environmental Class (During Operation):
class 3C3 according to IEC 60721-3-3 || class 3S3 according to IEC 60721-3-3
Number Of Addresses:
1-247 Modbus serial
Emc Filter:
integrated || with EMC plate option
With Safety Function Safe Programmable Logic:
FALSE
Noise Level:
56 dB
Continuous Output Current:
83 A 2.5 kHz normal duty || 66 A 2.5 kHz heavy duty
Operating Altitude:
<= 3280.84 ft (1000 m) without derating || 1000...4800 m with current derating 1 % per 100 m
Relative Symmetric Network Frequency Tolerance:
0.05
Base Load Current At High Overload:
66.0 A
Maximum Output Voltage:
690.0 V
Net Weight:
53 kg
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
With Safety Function Safely Limited Speed (Sls):
TRUE
Discrete Input Type:
DI1...DI8 programmable, 24 V DC <= 30 V)3.5 kOhm || DI7, DI8 programmable as pulse input 0-30 kHz, 24 V DC <= 30 V) || STOA, STOB safe torque off, 24 V DC <= 30 V)> 2.2 kOhm