Schneider Electric ATV930D11Y6 Atv930Ip00 11Kw 500V-690V Variable Spee
SKU:
ATV930D11Y6
UPC:
3.60648E+12
MPN:
Condition:
New
Circularity Profile:
ENVEOLI1704001EN
Communication Port Protocol:
Modbus TCP || EtherNet/IP || Modbus serial
Refresh Time:
relay output R1, R2, R3)5 ms +/- 0.5 ms)
Type Of Polarization:
no impedance
Upgradeability:
Upgraded components available
California Proposition 65:
WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov
Product Certifications:
TÃV || UL || CSA
Maximum Output Voltage:
690.0 V
Base Load Current At High Overload:
9.5 A
Local Signalling:
local diagnostic 3 LED mono/dual colour) || presence of voltage 1 LED red) || embedded communication status 3 LED dual colour) || communication module status 4 LED dual colour)
Power Dissipation In W:
forced convection 198 W 500 V 4 kHz || natural convection 98 W 500 V 4 kHz
Analogue Output Number:
2
Weee:
The product must be disposed on European Union markets following specific waste collection and never end up in rubbish bins.
Maximum Acceleration Under Vibrational Stress (During Operation):
10 m/s² at 13...200 Hz
Method Of Access:
slave Modbus TCP
Transmission Frame:
RTU
Discrete Output Type:
logic output DQ+ 0-1 kHz <= 30 V DC 100 mA || programmable as pulse output DQ+ 0-30 kHz <= 30 V DC 20 mA || logic output DQ- 0-1 kHz <= 30 V DC 100 mA
Permitted Relative Humidity (During Operation):
class 3K5 according to EN 60721-3
Data Format:
8 bits, configurable odd, even or no parity Modbus serial
Reach Regulation:
Reference contains Substances of Very High Concern above the threshold
Insulation Resistance:
> 1 MOhm 500 V DC for 1 minute to earth
Discrete Input Type:
DI1...DI8 programmable, 24 V DC <= 30 V)3.5 kOhm || DI7, DI8 programmable as pulse input 0-30 kHz, 24 V DC <= 30 V) || STOA, STOB safe torque off, 24 V DC <= 30 V)> 2.2 kOhm
With Safety Function Safe Stop 1 (Ss1):
TRUE
Depth:
242 mm
Exchange Mode:
half duplex, full duplex, autonegotiation Ethernet IP/Modbus TCP
slot A communication module Profibus DP V1 || slot A communication module PROFINET || slot A communication module DeviceNet || slot A communication module EtherCAT || slot A communication module CANopen daisy chain RJ45 || slot A communication module
Sampling Duration:
2 ms +/- 0.5 ms DI1...DI8) - discrete input || 5 ms +/- 1 ms DI7, DI8) - pulse input || 1 ms +/- 1 ms AI1, AI2, AI3) - analog input || 5 ms +/- 1 ms AQ1, AQ2) - analog output
Discrete Input Logic:
16 preset speeds
Minimum Switching Current:
relay output R1, R2, R3 5 mA 24 V DC
Shock Resistance:
15 gn 11 ms IEC 60068-2-27
Maximum Acceleration Under Shock Impact (During Operation):
150 m/s² at 11 ms
Pollution Degree:
2
[Us] Rated Supply Voltage:
500...690 V - 15...10 %
Environmental Disclosure:
ENVPEP1704001EN
Product Destination:
asynchronous motors || synchronous motors
Ambient Air Temperature For Operation:
-15-50 °C without derating) || 50-60 °C with derating factor)
Protection Type:
thermal protection motor || safe torque off motor || motor phase break motor || thermal protection drive || safe torque off drive || overheating drive || overcurrent between output phases and earth drive || overload of output voltage drive || short-c
Mercury Free:
Yes
Emc Filter:
integrated || with EMC plate option
Accuracy:
+/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input || +/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog output
relay output R1 resistive, cos phi = 1 3 A 250 V AC || relay output R1 resistive, cos phi = 1 3 A 30 V DC || relay output R1 inductive, cos phi = 0.4 7 ms 2 A 250 V AC || relay output R1 inductive, cos phi = 0.4 7 ms 2 A 30 V DC || relay output R2, R
With Safety Function Safely Limited Position (Slp):
external supply for digital inputs 24 V DC 19-30 V), <1.25 mA overload and short-circuit protection || internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10 mA overload and short-circuit protection || internal supply for d
Vibration Resistance:
1.5 mm peak to peak 2-13 Hz)IEC 60068-2-6 || 1 gn 13-200 Hz)IEC 60068-2-6
optimized torque mode || constant torque standard || variable torque standard
Connector Type:
2 RJ45 || 1 RJ45
Line Current:
13.6 A 500 V normal duty) || 10.4 A 500 V heavy duty) || 14.7 A 690 V normal duty) || 10.5 A 690 V heavy duty)
Analogue Input Type:
AI1, AI2, AI3 software-configurable voltage 0...10 V DC 30 kOhm 12 bits || AI1, AI2, AI3 software-configurable current 0...20 mA/4...20 mA 250 Ohm 12 bits
Relay Output Number:
3
Type Of Polarization:
no impedance Modbus serial
With Safety Function Safe Torque Off (Sto):
TRUE
Noise Level:
58 dB
Electromagnetic Compatibility:
electrostatic discharge immunity test level 3 IEC 61000-4-2 || radiated radio-frequency electromagnetic field immunity test level 3 IEC 61000-4-3 || electrical fast transient/burst immunity test level 4 IEC 61000-4-4 || 1.2/50 µs - 8/20 µs surge im
Motor Power Kw:
7.5 kW normal duty || 5.5 kW heavy duty
Linearity Error:
AI1, AI2, AI3 +/- 0.15 % of maximum value analog input || AQ1, AQ2 +/- 0.2 % analog output
Height:
420 mm
Physical Interface:
Ethernet || 2-wire RS 485
Synchronous Motor Control Profile:
permanent magnet motor || synchronous reluctance motor
Regulation Loop:
adjustable PID regulator
Net Weight:
22 kg
Braking To Standstill:
by DC injection
Environmental Class (During Operation):
class 3C3 according to IEC 60721-3-3 || class 3S3 according to IEC 60721-3-3
With Safety Function Safe Position (Sp):
FALSE
Range Of Product:
Altivar Process ATV900
Eu Rohs Directive:
Pro-active compliance (Product out of EU RoHS legal scope)
Prospective Line Isc:
70 kA
Product Specific Application:
process for industrial
Electrical Connection:
control screw terminal 0.5...1.5 mm² AWG 20...AWG 16 || DC bus screw terminal 4...10 mm² AWG 12...AWG 8 || line side screw terminal 4...10 mm² AWG 12...AWG 8 || motor screw terminal 4...10 mm² AWG 12...AWG 8
Brake Chopper Integrated:
TRUE
Motor Slip Compensation:
not available in permanent magnet motor law || automatic whatever the load || can be suppressed || adjustable
Number Of Addresses:
1-247
China Rohs Regulation:
X
Analogue Output Type:
software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits || software-configurable current AQ1, AQ2 0...20 mA 500 Ohm 10 bits