Description
Technical Data
Input
Number of phases
1
Rated voltage UN
AC 120/240 V (manual)
Operation voltage range
AC 90???132 V / AC 187???264 V, DC 270???345 V
Line frequency
47???63 Hz
Rated current IN
4 A @ AC 120 V / 2 A @ AC 240 V
Inrush current
<40 A
Internal fuse
T6, 3 A/AC 250 V
External fuse
Mini-circuit breaker: C 10 A / Safety fuse: T 10 A
Power Factor Correction P.F.C.
>0.6
Output
Rated voltage UN
DC24V
Rated current IN
10 A
Max. output current
13.5 A, 30 s
Heat dissipation
<35 W
Setting range Uout min./Uout max.
DC 23???27.5 V
Load regulation
<1 %
Ripple and Noise
<100 mV pp
Hold up time
>60 ms @ AC 120 V / >70 ms @ AC 240 V
Status indication DC ON LED green
???21.6 V
Status indication DC LOW LED red
???21.6 V
Parallel / redundant mode
yes/via external decoupling diode e.g. 722999
Efficiency
>87 %
Overtemperature protection
yes
Over voltage protection
>DC 33 V (UA=24 V)
Short circuit
Hiccup Mode
Monitoring
DC ON Control (Rdy)
N/O contact
Switching voltage
AC 300 V / DC 150 V
Switching current
AC/DC 1 A
Switching capacity
300 VA / 30 W
Isolation voltage
AC 500 V
General
Insulation voltage input / output
DC 4.2 kV
Insulation voltage input / ground
DC 2.2 kV
Insulation voltage output / ground
DC 750 V
Derating
>60 ???C: -5 W/???C
Operation temperature range
-20 ???C ??? +70 ???C (Derating)
Storage temperature range
-25???C???85???C
Cooling
Air convection, 50 mm distance top/bottom, 20 mm side
Housing material
Aluminum
Mounting
- DIN rail mountable TS35
- (EN 60715)
Installation position
vertical
Protection class
IP20 (IEC 529, EN 60529)
Over voltage category
III
Degree of polution
2
Weight
0,72 kg/piece
Connection type
- Screw terminal
- 0.20 mm2 ??? 2.5 mm2
- plug-in
Dimensions (w ?? h ?? d)
63??140??117 mm
Approvals
cULus (E249179)
Standards
- IEC 950
- EN 60950
- UL 60950
- EN 61000-6-2
- EN 61000-6-4
- EN 61000-4-2/3/4/5/6/11
PU
1 piece