Stationary access guarding,Stationary danger zone guarding
Functions:
Changeover between configurations,Configuration memory,Connection of up to 6 sensors,Deactivation of sensor groups,Slot for MicroSD card,Start/restart interlock (RES), selectable,Synchronization of controllers
Restart:
Automatic,Manual
SILCL:
2, IEC/EN 62061
Performance Level (PL):
d, EN ISO 13849-1
MTTFd:
42 years, EN ISO 13849-1
PFHD:
1.40E-08 per hour
Mission time:
20 years, EN ISO 13849-1
Category:
3, EN ISO 13849-1
Protective circuit:
External power supply unit with integrated short circuit protection,Overcurrent through integrated resettable fuse (max. 5s at 8A)
Supply voltage UB:
20 ... 28 V, DC
Current consumption, max.:
1,000 mA, Without external load
Power consumption, max.:
5 W
Number of safety-related switching outputs (OSSDs):