Stationary access guarding,Stationary danger zone guarding
Functions:
Changeover between configurations,Connection of up to 6 sensors,Deactivation of sensor groups,Start/restart interlock (RES), selectable,Synchronization of controllers
Restart:
Automatic,Manual
SIL:
2, IEC 61508
SILCL:
2, IEC/EN 62061
Performance Level (PL):
d, EN ISO 13849-1
MTTFd:
44 years, EN ISO 13849-1
PFHD:
4.5E-08 per hour
Mission time:
20 years, EN ISO 13849-1
Category:
3, EN ISO 13849-1
Protective circuit:
External power supply unit with integrated short circuit protection,Overcurrent through integrated resettable fuse (max. 5s at 8A)
Supply voltage UB:
20 ... 28 V, DC
Current consumption, max.:
1,000 mA, Without external load
Power consumption, max.:
5 W
Number of safety-related switching outputs (OSSDs):
2 Piece(s)
Type:
Ethernet, PROFINET
Function:
Parameterization
Function:
Process
PROFINET device:
Device acc. to Spec V2.3.5
GSDML:
GSDML acc. to Spec V2.3.5
Profile:
PROFINET/PROFIsafe
Conformance class:
C
Network load class:
III
Security level:
1
Switch functionality:
IRT-ready 2-port switch acc. to IEEE 802, integrated in connection unit